Single-phase DC-link reactor (1 line)
DESCRIPTION
Power Noise Reduction – save energy costs.
The DC-link reactor is used for smoothing the DC link current and to reduce mains harmonics in voltage source inverters.
The typical combinations of rectifiers and capacitors strains the supply network significantly. For functional reasons, the current consumption of the power supply or the inverter is not sinusoidal but pulsed at the moment of maximum voltage. DC-link reactor reduce the harmonics and relieve the supply network similar to the mains choke. In addition, the DC-link reactor attenuates charging current peak surges of the DC-link capacitors. By using a DC-link reactor the supply network is less burdened with harmonic reactive power.
Improvement of the efficiency of a converter (Power Factor Correction). Starting currents and current peak are attenuated up to 70%. Line reactors help to comply with international power quality standards IEEE 519 or EN 61000-3-2.
TYPICAL APPLICATIONS
Drive systems for motor drives,Mechanical engineering,Elevators/ escalators,Pipes,Conveyor technology,Ventilation and air conditioning,Robotics,Automation technology,Power supplies,Wind turbines
ADVANTAGES
- Reduction of harmonics waves
- Attenuation of current spikes of up to 70%
- Compact design
- Advantages over line reactor:
- Smaller size
- Lower cost of materials / Price
- Smaller power loss
- Production possible according to UL insulation system E251513
Technical Data
- Nominal voltage: U ≤ 600 V
- According to: EN 60289 / EN 61558
- Test voltage: L-PE 4000 V, AC/50Hz, 60s
- Insulation class: T40/F
- Protection rating: IP00
- Climatic category: DIN IEC 60068-1
- Overload: 1,5 x INenn 1 min / h
- Design: standing on foot angle
Type | Nominal voltage U [V] |
Nominal current [A] |
Inductance [mH] |
Power dissipation [W] |
Mass [kg] [kg] |
Weight Cu [kg] |
N CNW 891 / 8 | 600 50 / 60 Hz |
8 | 9,4 | 14 | 1,4 | 0,3 |
N CNW 891 /11 | 600 50 / 60 Hz |
11 | 6,2 | 15 | 2 | 0,3 |
N CNW 891 / 15 | 600 50 / 60 Hz |
15 | 4,8 | 20 | 2,8 | 0,6 |
N CNW 891 / 20 | 800 50 / 60 Hz |
20 | 3,3 | 19 | 3,6 | 0,6 |
N CNW 891 /28 | 800 50 / 60 Hz |
28 | 2,4 | 22 | 3,6 | 0,8 |
N CNW 891 / 34 | 800 50 / 60 Hz |
34 | 2,0 | 29 | 4,5 | 0,8 |
N CNW 891 / 40 | 800 50 / 60 Hz |
40 | 1,6 | 31 | 7 | 1 |
N CNW 891 / 55 | 800 50 / 60 Hz |
55 | 1,2 | 43 | 8 | 1,2 |
N CNW 891 / 70 | 800 50 / 60 Hz |
70 | 0,98 | 49 | 10,5 | 1,4 |
N CNW 891 / 85 | 800 50 / 60 Hz |
85 | 0,81 | 60 | 13,6 | 1,8 |
N CNW 891 / 100 | 800 50 / 60 Hz |
100 | 0,67 | 70 | 14 | 2,5 |
Type | Lenght L1 (mm) | Broad B1 (mm) | Broad B2 (mm) | High max. H (mm) | Mounting N1 (mm) | Attachment N2 (mm) | Attachment D1 (mm x mm) | Terminal connection/ cable lug [mm²] |
Connection PE | Connection A1 (mm) | Design |
N CNW 891 / 8 | 84 | 76 | 62 | 80 | 64 | 48 | 5 x 8 | 2,5 | Flat plug 6,3 x 0,8 | 1 | |
N CNW 891 /11 | 84 | 90 | 76 | 80 | 64 | 62 | 5 x 8 | 2,5 | Flat plug 6,3 x 0,8 | 1 | |
N CNW 891 / 15 | 96 | 95 | 88 | 85 | 84 | 72 | 6 x 11 | 2,5 | Flat plug 6,3 x 0,8 | 1 | |
N CNW 891 / 20 | 96 | 138 | 102 | 85 | 84 | 85 | 6 x 11 | 10 (m5) | M5 | 40 | 2 |
N CNW 891 /28 | 96 | 138 | 102 | 85 | 84 | 85 | 6 x 11 | 16 (M5) | M5 | 40 | 2 |
N CNW 891 / 34 | 105 | 138 | 105 | 95 | 84 | 87 | 6 x 11 | 16 (M5) | M5 | 40 | 2 |
N CNW 891 / 40 | 120 | 155 | 120 | 105 | 90 | 105 | 6 x 11 | 16 (M5) | M6 | 45 | 2 |
N CNW 891 / 55 | 150 | 138,5 | 107,5 | 135 | 122 | 87,5 | 7 x 13 | 16 (M5) | M6 | 45 | 2 |
N CNW 891 / 70 | 150 | 159 | 124,5 | 135 | 122 | 104,5 | 7 x 13 | 25 (M8) | M6 | 45 | 2 |
N CNW 891 / 85 | 150 | 185,5 | 150,5 | 135 | 122 | 130,5 | 7 x 13 | 25 (M8) | M6 | 45 | 2 |
N CNW 891 / 100 | 174 | 162,5 | 121 | 150 | 135 | 101 | 7 x 13 | 35 (M8) | M8 | 50 | 2 |