Through-hole current transformer (module base)

Description

With through-hole current transformers, the primary conductor provided by the customer is inserted through the current transformer opening in the housing. The through-hole opening is oriented to the primary current strength. Wound current transformers have a primary winding and a secondary winding. Both windings are applied to the closed ring core and separated from each other by insulation. This principle is predominantly used for small primary currents.

Advantages

  • Bolt or flat plug connection
  • Through-hole current transformer for direct conductor routing
  • Toroidal cores made of high-quality magnetic cores
  • Frequency range 16 2/3 to 400 Hz optional
  • High core output power and high-quality insulation
  • Electrically isolated primary and secondary circuits
  • Easy-to-install module housings
  • Variable connections, e.g., bolts, plugs, flat plugs, strands
  • Versatile housing options with different through-hole openings

Typical Applications

Industry, Renewable Energies, Railway Technology, Energy, Automation and Building Technology
Type IE modular 500 1000 2500
IPN Rated primary current 500 1000 2500 [A]
ImaxPN Max. rated primary current 600 1200 3000 [A]
IaN Secondary current 1000 [mA]
RB Burden resistance 5 15 30 [Ω]
URB Burden voltage 5 15 30 [V]
PSek Power 5 15 30 [VA]
KN Transformation ratio 500 1000 2500
Fi Measurement accuracy (50 Hz) 0,5 0,5 0,5 [%]
f Frequency 50-400 [Hz]
TA Ambient temperature -25 to +70 [°C]
Vp Insulation test 3 [KVac]
Connection MS-bolt / flat plug 6.3 x 0.8 [mm²]
Weight 0.8 0.8 1.8 [kg]
Standards 61869-2
Type I
[mm]
h1/h2
[mm]
t1/t2
[mm]
s1/s2
[mm]
b1/b2
[mm]
D
[mm]
D1xD2
[mm]
f
[mm]
e
[mm]
x1/x2
[mm]
IE modular 500 70 76/35 38/64 57/57 57/50 30,2 30.4×10.4 4,3 4,3 36/15
IE modular 1000 94 100/47 42/72 78/78 78/60 38,5 40.5×13.5 5,3 5,3 36/15
IE modular 2500 135 141/67,5 52/88 102/102 102/70 57,5 60.5×20.5 6,5 6,5 36/15